When India’s largest tractor maker Mahindra & Mahindra (M&M) was looking for an effective cooling solution for its workers and machines at the Nagpur plant, HMX-Ambiator provided the right system. A blow through type system with 32,000 CFM capacity.
HMX, a business unit of A.T.E., designs and manufactures unique, energy-efficient and eco-friendly products for space and process cooling for the industrial and commercial sectors, using its patented and highly successful DAMA technology. The product range includes the HMX-Ambiator, and the fresh air pre-cooling units, HMX-PCU-F and HMX-PCU-R. With an installation base of 20 million CFM all over India, HMX is making fast strides in providing eco-friendly cooling solutions for people and process comfort.
One such client that HMX helped to provide comfortable work environment with its innovative cooling solutions is Mahindra & Mahindra.
Mahindra & Mahindra (M&M) is the largest tractor manufacturer in the world (by volume). M&M has already sold over 2.1 million tractors. The manufacturing plant on Hingana Road, Nagpur, rolls out 90,000 tractors per year and is one of the largest tractor manufacturing units in India.
Challenge
M&M has more than one tractor assembly shop floor at its manufacturing plant in Nagpur. The factory management was using a 40 TR chilled water system for machine cooling and an air handling system (without cooling coil) for worker comfort at one of their tractor assembly areas. Though the chilled water system proved to be adequate for cooling the machines, it failed to provide comfort to the workers. This problem was further aggravated by the extreme summer conditions in Nagpur where temperatures soar up to 47°C. This led to frequent worker discomfort that resulted in loss of precious production hours.
Solution
When approached by M&M for a solution, the head of the R&D department of HMX visited the site. Upon investigation it was found out that in addition to inadequate chiller capacity, an improper layout of ducting and the resulting excessive losses in static pressure also contributed to the failure of the existing cooling system. It was decided to modify the existing ducting layout and install a HMX-Ambiator (blow through type) of 32,000 CFM capacity. Out of this, 16,000 CFM was going to be used for machine cooling and the remaining 16,000 CFM for people comfort. The management was facing a recurring problem of rusting of the blowers and motors on air washers in other parts of the factory. Most importantly, comfortable temperatures were also not being maintained on the shop floors due to the limitation of the single stage evaporative cooling. Hence M&M was searching for something better.
Ambiator performance:
Sr No | Date | Time | Ambient Temperature °C | Machine Outlet°C | Room°C | |||
DBT | WBT | DBT | WBT | DBT | WBT | |||
1 | 24/3/14 | 1.00 pm | 38 | 22 | 23 | 20 | 25 | 21 |
2 | 24/3/14 | 2.30 pm | 40 | 22 | 24 | 20 | 26 | 22 |
3 | 24/3/14 | 4.00 pm | 39 | 23 | 25 | 21 | 27 | 23 |